APC Symmetra, 2800 Watts / 4000 VA,Input 208V / Output 208V, Interface Port DB-9 RS-232, RJ-45 10 Base-T ethernet for web/ SNMP/ Telnet management, Extended runtime model, Rack Height 8 U
| Technical Specifications |
Technical Details |
| Output |
| Output Power Capacity |
2800 Watts / 4000 VA |
 |
| Max Configurable Power |
4200 Watts / 6000 VA |
 |
| Nominal Output Voltage |
208V |
 |
| Output Voltage Note |
Configurable for 208 or 240 nominal output voltage |
 |
| Efficiency at Full Load |
89.00% |
 |
| Output Voltage Distortion |
Less than 5% at full load |
 |
| Output Frequency (sync to mains) |
57 - 63 Hz for 60 Hz nominal |
 |
| Crest Factor |
up to 5 : 1 |
 |
| Waveform Type |
Sine wave |
 |
| Output Connections |
(2) NEMA L6-20R |
 |
| (1) NEMA L6-30R |
 |
| Input |
| Bypass |
Internal Bypass (Automatic and Manual) |
 |
| Nominal Input Voltage |
208V |
 |
| Input Frequency |
50/60 Hz +/- 5 Hz (auto sensing) |
 |
| Input Connections |
Hard Wire 3-wire (2PH + G) |
| NEMA L6-30P (30A Twist-Lock) |
 |
| Cord Length |
6 feet (1.83 meters) |
 |
| Input voltage range for main operations |
155 - 276V |
| Batteries & Runtime |
| Battery Type |
Maintenance-free sealed Lead-Acid battery with suspended electrolyte : leakproof |
 |
| Included Battery Modules |
2 |
 |
| Available Battery Slots |
2 |
 |
| Typical recharge time |
4 hour(s) |
 |
| Replacement battery cartridge |
SYBT2 |
 |
| Replacement battery cartridge note |
UPS accepts 1-2 additional battery packs |
 |
| Typical Backup Time at Half Load |
30.2 minutes (1400 Watts) |
 |
| Typical Backup Time at Full Load |
12.7 minutes (2800 Watts) |
 |
| Runtime Chart |
Symmetra |
 |
| Extended Run Options |
APC Symmetra RM 4kVA Scalable to 6kVA N+1 208/240V |
| Communications & Management |
| Interface Port(s) |
DB-9 RS-232,RJ-45 10 Base-T ethernet for web/ SNMP/ Telnet management |
 |
| Available SmartSlot™ Interface Quantity |
1 |
 |
| Pre-Installed SmartSlot™ Cards |
AP9619 |
 |
| Control panel |
Multi-function LCD status and control console |
 |
| Audible Alarm |
Alarm when on battery : distinctive low battery alarm : configurable delays |
 |
| Emergency Power Off (EPO) |
Yes |
| Physical |
| Maximum Height |
14.00 inches (356 mm) |
 |
| Maximum Width |
19.00 inches (483 mm) |
 |
| Maximum depth |
28.75 inches (730 mm) |
 |
| Rack Height |
8U |
 |
| Net Weight |
229.00 lbs. (104.09 kg) |
 |
| Shipping Weight |
256.00 lbs. (116.36 kg) |
 |
| Shipping Height |
20.00 inches (508 mm) |
 |
| Shipping Width |
23.00 inches (584 mm) |
 |
| Shipping Depth |
31.00 inches (787 mm) |
 |
| Color |
Black |
| Environmental |
| Operating Environment |
32 - 104 °F (0 - 40 °C) |
 |
| Operating Relative Humidity |
0 - 95% |
 |
| Operating Elevation |
0-10000 feet (0-3000 meters) |
 |
| Storage Temperature |
5 - 113 °F (-15 - 45 °C) |
 |
| Storage Relative Humidity |
0 - 95% |
 |
| Storage Elevation |
0-50000 feet (0-15000 meters) |
 |
| Audible noise at 1 meter from surface of unit |
60.00 dBA |
 |
| Online Thermal Dissipation |
1181.00 BTU/hr |
| Conformance |
| Regulatory Approvals |
CSA,FCC Part 15 Class A,UL 1778 |
 |
| Standard Warranty |
2 years repair or replace,optional on-site warranties available,optional extended warranties available |