APC Smart-UPS RT, 6400 Watts / 8000 VA,Input 208V / Output 120V, 208V, Interface Port DB-9 RS-232, RJ-45 10/100 Base-T, Smart-Slot, Extended runtime model, Rack Height 8 U
| Technical Specifications |
Technical Details |
| Output |
| Output Power Capacity |
6400 Watts / 8000 VA |
 |
| Max Configurable Power |
6400 Watts / 8000 VA |
 |
| Max Configurable Power |
120V,208V |
 |
| Output Voltage Note |
Configurable for 208 or 240 nominal output voltage |
 |
| Output Voltage Distortion |
Less than 3% |
 |
| Output Frequency (sync to mains) |
50/60 Hz +/- 3 Hz user adjustable +/- 0.1 |
 |
| Crest Factor |
3 : 1 |
 |
| Waveform Type |
Sine wave |
 |
| Output Connections |
(1) Hard Wire 3-wire (2PH + G) |
| (12) NEMA 5-20R |
 |
| (2) NEMA L6-20R |
 |
| (1) NEMA L6-30R |
 |
| Input |
| Bypass |
Internal Bypass (Automatic and Manual) |
 |
| Nominal Input Voltage |
208V |
 |
| Input Frequency |
50/60 Hz +/- 5 Hz (auto sensing) |
 |
| Input Connections |
Hard Wire 3-wire (2PH + G) |
 |
| Input voltage range for main operations |
160 - 280V |
| Batteries & Runtime |
| Battery Type |
Maintenance-free sealed Lead-Acid battery with suspended electrolyte : leakproof |
 |
| Included Battery Modules |
4 |
 |
| Typical recharge time |
2.20 hour(s) |
 |
| Replacement battery cartridge |
RBC44 |
 |
| RBC™ Quantity |
2 |
 |
| Typical Backup Time
at Half Load |
17.9 minutes (3200 Watts) |
 |
| Typical Backup Time
at Full Load |
6.3 minutes (6400 Watts) |
 |
| Runtime Chart |
Smart-UPS RT |
 |
| Extended Run Options |
APC Smart-UPS RT 8000VA RM 208V w/ 208V to 120V 2U Step-Down Transformer |
| Communications & Management |
| Interface Port(s) |
DB-9 RS-232,RJ-45 10/100 Base-T,Smart-SlotDB-9 RS-232,RJ-45 10/100 Base-T,Smart-Slot |
 |
| Pre-Installed SmartSlot™ Cards |
AP9619 |
 |
| Control panel |
LED status display with load and battery bar-graphs and On Line : On Battery : Replace Battery : Overload and Bypass Indicators |
 |
| Audible Alarm |
Alarm when on battery : distinctive low battery alarm : overload continuous tone alarm |
 |
| Emergency Power Off (EPO) |
Yes |
| Surge Protection and Filtering |
| Filtering |
Full time multi-pole noise filtering : 0.3% IEEE surge let-through : zero clamping response time : meets UL 1449 |
| Physical |
| Maximum Height |
13.85 inches (352 mm) |
 |
| Maximum Width |
17.00 inches (432 mm) |
 |
| Maximum depth |
26.12 inches (663 mm) |
 |
| Rack Height |
8U |
 |
| Net Weight |
345.00 lbs. (156.82 kg) |
 |
| Shipping Weight |
402.00 lbs. (182.73 kg) |
 |
| Shipping Height |
31.75 inches (806 mm) |
 |
| Shipping Width |
23.50 inches (597 mm) |
 |
| Shipping Depth |
39.00 inches (991 mm) |
 |
| Color |
Black |
| Environmental |
| Operating Environment |
32 - 104 °F (0 - 40 °C) |
 |
| Operating Relative Humidity |
0 - 95% |
 |
| Operating Elevation |
0-10000 feet (0-3000 meters) |
 |
| Storage Temperature |
5 - 113 °F (-15 - 45 °C) |
 |
| Storage Relative Humidity |
0 - 95% |
 |
| Storage Elevation |
0-50000 feet (0-15000 meters) |
 |
| Audible noise at 1 meter from surface of unit |
55 dBA |
 |
| Online Thermal Dissipation |
1535.00 BTU/hr |
| Conformance |
| Regulatory Approvals |
CSA,FCC Part 15 Class A,UL 1778 |
 |
| Standard Warranty |
2 years repair or replace |